<< Click to Display Table of Contents >> Transformer Details |
![]() ![]()
|
![]()
Field |
Field Description |
Quantity |
Quantity of selected transformer type to be modelled in parallel |
Description |
Built automatically from the other specifications |
![]()
Auto Transformer |
Switch the selected transformer into an Autotransformer with the facility to specify grounding. If this is checked, a "Grounded" check box appears, which, in turn, affects the "Vector Group & Grounding Groupbox. |
Rating |
Normal Rating of the Transformer in MVA. This rating is ONAN (Oil Natural, Air Natural). |
Primary Voltage |
The primary voltage of the transformer |
Secondary Voltage |
The secondary voltage of the transformer |
Overload |
Permissible transformer overload in pu. This can be used to indicate the transformer's emergency rating or ONAF, OFAF, etc. rating. (Oil Forced, Air Forced) |
% Internal Boost |
Specify the percentage internal voltage boost of the transformer |
User Code |
Definable User Code |
![]()
Positive Sequence Impedance % |
Positive sequence impedance in percentage from the transformer's name plate information |
Positive Sequence X to R ratio |
Positive sequence Reactance to Resistance ratio. |
Zero Sequence Impedance % |
Zero sequence impedance in percentage from the transformer's name plate information |
Zero Sequence X to R ratio |
Zero sequence Reactance to Resistance ratio. |
![]()
No Load Loss |
As a % of the Transformer rating |
No Load Current |
As a % of the Rated Current |
Zo Magnetizing |
Zero Sequence Magnetizing that will be used in Y/YN or YN/Y fault calculations |
![]()
HV Transformer Type / Earthing |
Transformer Type and Earthing arrangement for the primary windings of the transformer, eg : Star earthed would be : YN. |
HV Earthing Impedance |
Impedance values for the primary earthing equipment |
HV Earthing Reactance |
Reactance values for the primary earthing equipment |
LV Transformer Type / Earthing |
Transformer Type and Earthing arrangement for the secondary windings of the transformer, eg : Delta earthed would be : DN. |
LV Earthing Impedance |
Impedance values for the secondary earthing equipment |
LV Earthing Reactance |
Reactance values for the secondary earthing equipment |
HV-LV Phase Shift (deg) |
Angle Phase shift of the Transformer from Primary to Secondary |
![]()
Primary / Secondary Tap |
Specify whether the tap is on the primary or secondary winding of the transformer |
Physical Taps |
Choice between physical or percentages for tap positions and specifications |
Lock Tap |
Prevent or allow tap position from changing automatically |
Number |
Total number of taps available to tap |
Nominal |
The nominal tap position of the tap changer |
Step |
the % voltage step value of the tap changer |
Position |
The selected tap position of the tap changer |
Minimum Voltage |
Minimum voltage as a percentage for the tap change control |
Maximum Voltage |
Maximum voltage as a percentage for the tap change control |
Controlled Bus |
Select a bus for line drop compensation control. |
![]()